Kitchen Exhaust Duct Cleaning Maintenance
Maintenance Information
Mandatory Maintenance Intervals
Maintenance is required by law every six months, but the specific volume of cooking may require more frequent service:
-
Monthly: Systems serving solid fuel cooking operations.
-
Quarterly: High-volume operations (e.g., 24-hour cooking, charbroiling, or wok cooking).
-
Semiannually: Systems serving moderate-volume cooking operations.
-
Annually: Low-volume operations (e.g., churches, day camps, or senior centers).
The "Bare Metal" Cleaning Standard
The industry standard for compliance is "bare metal clean" throughout the entire system.
-
Scope: Cleaning must include the floor, backsplash, appliances, hood, plenum, ducts, fans, fan housing, and roof discharge areas.
-
Personnel: Inspection and cleaning must be conducted by a properly trained, qualified, and certified company or person(s) authorized by the State or Local Fire Marshal.
-
Duct Access: Systems must have access panels installed no more than 20 feet apart, or 10 feet apart at changes of direction.
Post-Service Documentation for Owners
Upon completion, owners must receive these four items to verify compliance:
-
Completion/Deficiency Report: Detailing any areas not cleaned or existing system problems.
-
Photographic Evidence: Before and after photos showing the entire system from floor to roof.
-
Detailed Invoice: Itemizing the work accomplished and the final contract price.
-
Conspicuous Label: Placed on the hood with technician details and service dates.
Service Label Specifications - Physical Requirements
The service sticker is provided by the licensee/contractor and must meet these minimum qualifications:
-
Dimensions: Exactly 5.5 inches by 4.5 inches.
-
Color: Any color except RED with contrasting text.
-
Material: Writeable, heat-resistant, self-destructing material with self-sticking adhesive.
-
Placement: Placed conspicuously on the hood in the immediate vicinity of the suppression system tag.
Pre-Printed Content Requirements
The label must be pre-printed with the following verbatim information:
-
Mandatory Notice: "DO NOT REMOVE BY ORDER OF THE STATE FIRE MARSHAL".
-
Company Information: Full address and a 24-hour emergency service contact phone number.
-
Licensing: Fire Marshal’s Seal of Registration and the Concern License ("K") number.
Technician Completion Fields
When service is performed, the following must be clearly filled out or punched:
-
Date of Service: Full date (year, month, and day).
-
Service Type: Clearly indicating if the system was "Inspected" or "Cleaned".
-
Next Service Due: Must be clearly hand-punched into the label (interval not to exceed five years).
-
Technician Identity: Printed name, original signature, and Certificate of Registration "KEE" number.
For additional information on the Kitchen Exhaust Cleaning & Inspection Program, contact Russ Sneddon, Deputy State Fire Marshal, 385-434-9609 or [email protected].